Modbus Plus to IEC 60870-5-101 Slave Communication Module
5301-MBP-101S
Product Description
The ProLinx family Modbus Plus to IEC 60870-5-101 Slave communications module (5301-MBP-101S) creates a powerful connection between devices on a Modbus Plus network and an IEC 101 master device. The module is a stand-alone DIN-rail mounted protocol gateway that provides one Modbus Plus configurable DB9F port and one IEC 101 Slave configurable serial port.
The IEC 60870-5-101 Slave (101S) protocol driver supports Slave implementations of the protocol. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.
Product Applications
The MBP-101S modules are the ideal solution for the many applications where Modbus Plus connectivity can be used to integrate an IEC 101 master device into a system.
The Modbus Plus gateway is a powerful module designed with both Master and Slave support, enabling easy connection to other Modbus devices (Modicon processors and many others). In combination with the IEC 101 Slave support, the module provides a very powerful interface to the many IEC 101 master devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially the Manufacturing, Oil and Gas, Electrical Power and Food Processing.
Functional Specifications
Internal Database
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
Application Data Area
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
Status Data Area
This area is used to store error codes, counters, and port status information for each port.
Configuration Data Area
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
Modbus Plus Port Specifications
The Modbus Plus (MBP) protocol driver operates as a single, peer-to-peer Modbus Plus port with dual media-redundant connectors. The two connectors cannot be configured as separate MBP ports. They are for physical cabling redundancy only.
|
General Parameters
|
|
Modbus Function Codes
|
3 : Read Multiple Data Registers (MSTR 2)
16 : Write Multiple Data Register (MSTR 1)
Global data read (32 words max.)
Global data write (32 words max.)
|
|
Address Scope
|
1-64
|
|
Modbus Plus Functioning as a Master
|
|
Command List
|
Up to 200 commands on the master port, fully configurable for function, slave address, register to/from addressing and word count
|
|
Status Data
|
Error codes available on an individual command basis. In addition, a slave status list is maintained per active Modbus Master port.
|
|
Polling of command list
|
Configurable polling of command list, including continuous and on change of data
|
|
Modbus Plus Functioning as a Slave
|
|
Node address
|
1 to 64 - software selectable
|
|
Status Data
|
Error codes, counters and port status available on the configured slave port
|
IEC 60870-5-101 Slave Protocol Specifications
The 101S module acts as a gateway between the IEC-870-5-101 other protocols and networks, as well as several proprietary interfaces.
General specifications include:
- User-definable module memory usage
- Storage of IEC time used in module is available in the database
- Protocol implementation conforms to the IEC-870-5-101 specification with fully configurable parameters
- Priority Queues
- Invalid Bit Monitoring
- Supports Balanced and Unbalanced Mode
- Supports CP24 and CP56 time formats for events
- Event generation configurable per point or data type
|
General Parameters
|
|
Communication parameters
|
Baud Rate: 110 to 38,400 baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd RTS Timing Delays: 0 to 65535 ms
|
|
IEC 870-5-101 Slave
|
|
Configurable Parameters
|
Data link address length
Common Address of ASDU length
Inform. Object Address length
Select/Operate Timeout
Event Scan delay
Use Balanced Mode
Short Pulse Time
Long Pulse Time Time DB Offset
|
|
Status Data
|
Status data is returned in a block of counter values allowing communications to be effectively debugged.
|
|
Supported Data Types
|
M_SP_NA
M_DP_NA
M_ST_NA
M_ME_NA
M_ME_NB
M_ME_NC
M_IT_NA
C_SC_NA
C_DC_NA
C_RC_NA
C_SE_NA
C_SE_NB C_SE_NC
|
Hardware Specifications
| Power Supply |
24 VDC nominal |
| |
18-32 VDC allowed |
| |
Positive, Negative, GND Terminals |
| |
2.5 mm screwdriver blade |
Current Load
|
500 mA max@ 32 VDC max |
| Operating Temperature |
-20 to 50°C |
| |
-4 to 122°F |
|
Storage Temperature |
-40 to 85°C |
| |
-40 to 185°F |
| Relative Humidity |
5% to 95% (non-condensing) |
| Dimensions |
Standard
5.20H x 2.07W x 4.52D inches
13.2cmH x 5.25cmW x 11.48cmD
Extended
5.20H x 2.73W x 4.52D inches
13.2cmH x 6.934cmW x 11.48cmD |
|
LED Indicators |
Power and Module Status |
| |
Application Status |
| |
Serial Port Activity LED |
| |
Serial Activity and Error LED Status |
| Configuration Serial Port |
DB-9M RS-232 only |
| |
No hardware handshaking |
Ethernet Port (Ethernet protocol gateways only) |
10Base-T half duplex RJ45 Connector |
| |
Link and Activity LED indicators |
| |
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
| |
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration |
|
Application Serial Ports (Serial protocol gateways only) |
RS-232/422/485 |
| |
RS232 handshaking configurable |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor |
| |
Note: The number of serial application ports depends on the module type, and the combination of protocols. |
|
Serial Port Isolation |
2500V RMS port signal isolation per UL 1577 |
| |
3000V DC min. isolation port to ground and port to logic |
|
Shipped with each unit |
Mini-DIN to DB-9M serial cables |
| |
4 ft RS-232 configuration cable |
| |
2.5mm screwdriver |
| |
CD (docs and Configuration utility) |
| |
RS-422/485 DB-9 to Screw Terminal Adaptor for each serial application port (serial protocols only) |
Click here for dimensions diagram Certifications
The ProLinx gateway module has the following certifications:
CE
ATEX Cat 3 Zone 2
cULus Haz Loc Class I, Div 2
Ordering Information
|
5301-MBP-101S
|
Modbus Plus to IEC60870-5-101 Slave
|
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.