ProSoft Technology, Inc.
Home > Products > Industrial Wireless > Frequency Hopping > RLX-IFH9S
Printable Page
 

Search | Clear


RadioLinx Industrial Frequency Hopping 900 MHz Serial

RLX-IFH9S

The RadioLinx Industrial Frequency Hopping 900 MHz Serial radio provides powerful and secure wireless serial communications and is well suited for demanding, long-range (up to 30+ miles) SCADA and other serial applications in tough environments. Operating in the license-free 900 MHz band, the RLX-IFH9S penetrates foliage and walls / ceilings better than higher frequency radios. With both RS-232 and RS-485 serial ports, serial protocols such as Modbus RTU, DF1, ASCII and DNP3 are supported. The RLX-IFH9S is user configurable as a master, repeater and remote radio and employs the 128 bit AES encryption algorithm approved by the United States government for top secret information.

RadioLinx Industrial Frequency Hopping 900 MHz Serial radios are quickly and easily configured using the included, graphical ControlScape software. An OPC server software is also included and allows users to monitor radio network health with any OPC client based HMI software.

Features and Benefits

Feature

Benefit

Powerful 900 MHz Serial

  • 230 kbps RF data rate at up to 30+ miles
  • Longer wavelength of the unlicensed 900 MHz band for superior wireless signal propagation vs. higher frequency unlicensed wireless bands

Rugged and Powerful

  • Up to one watt transmit power for long distance
  • Programmable frequencies to co-exist with other wireless networks or avoid interference
  • Metal enclosure, industrial operating temperatures, vibration and shock resistant
  • Certified for use in hazardous locations (ISA 12.12.01 Class I Div 2)

Strong Data and Network Security

  • 128 bit AES Encryption
  • Proprietary FHSS not detected by 802.11 wireless

Easy to Configure and Monitor

  • Graphical representation of network for configuration and diagnostics
  • Advanced diagnostics including VSWR, temperature, and signal quality
  • Included OPC Server for HMI-based RF network diagnostics

Backed by ProSoft Technology

  • Industrial data communications experts who understand your protocols, devices, and applications
  • Indoor/outdoor radio network design assistance - accessory selection, path studies, and site survey
  • Three year standard warranty

Configuration

The RadioLinx ControlScape FH application provides a graphical representation of your RadioLinx Frequency Hopping radio network, allowing you to easily configure the radios and monitor their performance. ControlScape can be used to support configuration and installation as well as provide long-term monitoring of system performance.

General Specifications

Radio

Frequency

902-928 MHz

Security

128 bit AES encryption

Network Topology

Point-to-point, point-to-multipoint, store and forward repeater

Error Detection

32 bit CRC, ARQ (Automatic Resend Query)

Radio Type

Frequency Hopping Spread Spectrum

Transmit Power (Programmable)

100 mW to 1 W
20 dBm to 30 dBm

Channel data rates (Programmable)

230, 172, 115 or 19.2 kbps

Receiver Sensitivity (Typical)

230 kbps: -106 dBm @ 10-6 BER
172 kbps: -108 dBm @ 10-6 BER
19.2 kbps: -116 dBm @ 10-6 BER

Outdoor Range

30+ miles pt-pt with high gain directional antennas and RF line-of-sight

Hardware Specifications

Enclosure

Extruded aluminum with DIN and panel mount

Size

104 x 94 x 53 mm (W x H x D)
4.1 x 3.7 x 2.1 inches

Vibration

IEC 60068 2-6 (20g, 3-Axis)

Shock

IEC 60068 2-27 (5g, 10Hz to 150Hz)

Serial Data Ports (2)

DB9, RS-232

RS-422 and RS-485

300 bps to 230 kbps

Configuration Port

DB9, RS-232

Antenna Ports

(1) RP-SMA connector

Weight

1.0 lbs (454 g)

Environmental

Operating Temperature

-40° C to +75° C

Humidity

up to 100% RH, without condensation

External Power

9Vdc to 30Vdc

Power Consumption

12 W peak

Agency Approvals & Certifications

UL

ISA 12.12.01 Class I Div 2 Groups A, B, C & D, T5.
Must be installed inside an IP54 enclosure that requires tool access.

CSA/cUL

C22.2 No. 213-M1987

ATEX

ATEX Category 3, Zone 2
II 3 G
Ex nA IIC T4 X
-30 C <= Ta <= +60 C

Ordering Information

RLX-IFH9S RadioLinx Industrial Frequency Hopping 900 MHz Serial
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Home : Products : Support : Distributors : Services : News/Events : Contact : ProSoft Tested