ProSoft Technology, Inc.
Home > Products > for Schneider Electric > PTQ-DNP
Printable Page
 

Search | Clear


DNP 3.0 Master/Slave Network Interface Module for Quantum

PTQ-DNP

The DNP 3.0 Master/Slave Network Interface Module for Quantum is a single slot, backplane compatible DNP 3.0 interface solution for the Schneider Electric Quantum or Unity platform. This module provides highly configurable support of both DNP 3.0 Master and Slave implementations.

Features and Benefits

The module supports DNP Subset Level 2 features and some of the Level 3 features allowing the many SCADA and field devices supporting the DNP protocol to be integrated into the Quantum or Unity platform. The module acts as an input/output module between the DNP network and the Modicon backplane. The data transfer from the Quantum or Unity processor is asynchronous from the actions on the DNP network. Databases are user defined and stored in the module to hold the data required by the protocol.

General Specifications

  • Single Slot - Quantum backplane compatible
  • The module is recognized as an Options module and has access to PLC memory for data transfer
  • Configuration data is stored in non-volatile memory in the ProTalk module
  • Configuration software for Microsoft Windows XP, 2000 and NT is included with the module.
  • Up to six modules can be placed in a rack
  • Local rack - The module must be placed in the same rack as processor.
  • Compatible with all common Quantum programming packages, including Concept (version 2.6 or higher), Unity Pro (version 2.2 or higher), ProWORX (version 2.20 or later), andModSoft.
  • Quantum data types supported: 0x, 1x, 3x, 4x
  • High speed data transfer across backplane provides quick data update times.
  • Sample function blocks available.

Applications

The PTQ-DNP module is the ideal solution for many applications where DNP 3.0 Master/Slave protocol connectivity must be added to a Modicon Quantum system.

The DNP solution is designed to address the expanding interest in the DNP 3.0 protocol. The protocol was developed for the Power Utility industry and is recommended by the IEEE for RTU-IED communication applications. Additional industrial applications are quickly arising in the Water/Wastewater and Oil and Gas industries.

Functional Specifications

The module has two DNP protocol ports that can be configured to operate in a Master/Slave or Slave/Slave redundant port configuration. User defined internal register space is accessible to the protocol driver and to the Quantum processor memory.

Redundant Slave Port Operation

When configured in the Slave/Slave port configuration, the module's slave ports operate in a primary and secondary fashion. In this mode, a single host polls the module via redundant physical layer connections.

DNP 3.0 Slave Protocol Specifications

  • The DNP Slave port accepts DNP commands to control and monitor data stored in the module's DNP Slave databases. If a DNP Master port is configured, a portion of the slave databases can be derived from or can control IED devices connected to the DNP master port.
  • Report-by-Exception data is logged to the module's database
  • Supports unsolicited messaging
  • Each DNP point type is user configurable by point
  • Class assignments are completely user-definable on a Type and point basis (BI, AI, FI, DI point types
  • Supports clock synchronization from a master or from the processor
  • Support for four octet-strings are supported (object type 110) in the slave driver to return version and other module information
  • Up to 400 events are stored for Floats, Binary In, Analog In and Double Inputs
  • Configurable event buffer transmission threshold based on count and/or time since last event transmission
  • Collision avoidance for redundant port switching
  • Special modem AT command string and timing support for dialing out on redundant port.

DNP 3.0 Master Protocol Specifications

  • The DNP 3.0 Master port can be configured as a virtual DNP Master device that actively issues user-defined DNP commands to nodes on the network.
  • Supports 300 user defined commands
  • Master port logically supports up to 40 slave devices
  • Individual command configuration includes conditional or continuous polling, Poll Delay Time
  • Slave status and Command status available for transfer to the processor
  • Event data received from the slave devices updates the module database (Date and Time stamping is not stored or used by module)
  • Special command handling for Digital Output CROB under processor control for pulse output control
  • Supports Report-by-Exception and Unsolicited Responses on a Time Interval basis or on a user determined Event Count basis. Analog and Binary input points are supported.

DNP 3.0 ports (PRT1 & PRT2)

  • Memory usage is user definable
  • Full radio, modem and multidrop support
  • Support for the storage and transfer of all DNP data types across the backplane.

Hardware Specifications

Backplane Current Load

1100 mA maximum @ 5 Vdc ± 5%

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Relative Humidity

5% to 95% (without condensation)

Vibration

Sine vibration 4 to100 Hz in each of the three orthogonal axes

Shock

30g, 11 mSec. in each of the three orthogonal axes

Dimensions (HxWxD), Approx

250 x 103.85 x 40.34 mm
9.84 x 4.09 x 1.59 in

LED Indicators

Module Status
Backlane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status

Configuration Serial Port
(PRT1)

DB-9M PC Compatible
RS-232 only
No hardware handshaking

Serial Ports

(PRT2, PRT3)
DB-9M PC Compatible
RS-232/422/485 jumper selectable
RS-422/485 screw termination included
RS-232 handshaking configurable
500 V Optical isolation from backplane

Ordering Information

PTQ-DNP DNP 3.0 Master/Slave Network Interface Module for Quantum
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe/Middle East/Africa
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 