EtherNet/IP Network Interface Module for Quantum
PTQ-DFNT
The EtherNet/IP Network Interface Module for Quantum is a Quantum backplane compatible module that allows Modicon Quantum processors to interface easily with EtherNet/IP protocol (Explicit Messaging) compatible devices and hosts. Devices commonly supporting the protocol include Rockwell Automation PLCs, and host HMI systems.
Features and Benefits
The PTQ-DFNT module is a single slot solution that provides a powerful connection between Schneider Electric's Quantum and Unity processors and EtherNet/IP network applications.
The module can send read or write commands to remote devices on the EtherNet/IP network. The PTQ-DFNT also has 20 servers that allows the module to receive commands from remote devices. Up to 100 commands can be configured by the user.
The PTQ-DFNT module is a powerful communication interface for Quantum platform processors. Developed under license from Schneider Electric, the module incorporates proprietary backplane technology that enables powerful data access to the Quantum processor.
General Specifications
- Single Slot - Quantum backplane compatible
- The module is recognized as an Options module and has access to PLC memory for data transfer
- Configuration data is stored in non-volatile memory in the ProTalk module
- Configuration software for Microsoft Windows XP, 2000 and NT is included with the module.
- Up to six modules can be placed in a rack
- Local rack - The module must be placed in the same rack as processor.
- Compatible with all common Quantum programming packages, including Concept (version 2.6 or higher), Unity Pro (version 2.2 or higher), ProWORX (version 2.20 or later), andModSoft.
- Quantum data types supported: 0x, 1x, 3x, 4x
- High speed data transfer across backplane provides quick data update times.
- Sample function blocks available.
EtherNet/IP (Explicit Messaging) Compatible Devices
List of Rockwell Automation material that support EPIC:
- PLC5/E rev C/N, D/E, E/D
- SLC5/05 series A, OS503 frn4
- 1785-ENET Series A, rev D
- Interchange V6.2
- MicroLogix 1100/1400/ANY via 1761-NET-ENI
- CompactLogix 1768-L43/L45 via 1768-ENBT
- CompactLogix 1769-L32E/L35E/ANY via 1761-NET-ENI
- RSLinx Gateway V1.7+
- ControlLogix 1756-ENET/ENBT/EN2T
Functional Specifications
|
Type
|
Specifications
|
|
Internal Database
|
4000 registers (words) available for transfer to and from Quantum processor
|
|
Modes
|
Client and Server supported
|
|
Messaging
|
PCCC on CIP - See command list that follows
CIP Services (Server Only) - See command list below
|
|
Service Port
|
AF12Hex (44818)
|
|
Compatibility
|
Compatible devices include a wide assortment of other client/server devices such as:
- PLC: PLC5/E Rev. C/N, D/E, E/D or later,1785-ENET Series A, Rev. D
- SLC: SLC5/05 Series A, OS501 fm5 or later
- CLX: 1756-ENET, 1756-ENBT
- CPLX: 1769-L5335E Rev. 12.26 Interchange (limited - Contact Tech Support)
- RSLinx: Gateway V1.7 or later
|
|
Miscellaneous
|
125 word read and write data lengths
Floating point data supported
|
EtherNet/IP Server Specifications
When in the Server mode, the module accepts commands from a Client(s) to read/write data stored in the module's internal registers. This data is easily transferred to the Quantum processor's data registers.
The EtherNet/IP functionality supported by the module includes:
|
EtherNet/IP Server
|
|
Connections
|
Twenty independent TCP server sockets permit remote clients to interact with all data contained in the module. Data can be derived from other clients on the network, through the client on the module, or from the Quantum processor
|
|
Data File
|
Data Table File Start - Fixed at N10
Data Table File Size - 100 or 1000 words
Data Table location in PTQ - Start Register 0
|
EtherNet/IP Client Specifications
When configured in the client mode the DFNT module is capable of reading and writing data to remote EtherNet/IP devices, enabling the Quantum platform to act as a SCADA sub-master.
The EtherNet/IP Client functionality supported by the module includes:
|
EtherNet/IP Client Specifications
|
|
Messaging
|
PCCC on CIP
Explicit Messaging supported
|
|
General
|
One client configurable for timing and commands
|
|
Command List
|
Up to 100 command, each fully configurable for function, slave address, register to/from addressing and word/bit count
|
|
Polling of command list
|
User configurable polling of commands, including disabled, continuous and on change of data (write only)
|
Hardware Specifications
|
Backplane Current Load
|
1100 mA maximum @ 5 Vdc ± 5%
|
|
Operating Temperature
|
0°C to 60°C
|
|
|
32°F to 140°F
|
|
Storage Temperature
|
-40°C to 85°C
|
|
|
-40°F to 185°F
|
|
Relative Humidity
|
5% to 95% (without condensation)
|
|
Vibration
|
Sine vibration 4 to100 Hz in each of the three orthogonal axes
|
|
Shock
|
30G, 11 mSec. in each of the three orthogonal axes
|
|
Dimensions (HxWxD), Approx.
|
250 x 103.85 x 40.34 mm 9.84 x 4.09 x 1.59 in
|
|
LED Indicators
|
Module Status
|
|
|
Backplane Transfer Status
|
|
|
E Link LED
|
|
|
E Data LED
|
|
Configuration Serial Port (PRT1)
|
DB-9M PC Compatible
|
|
|
RS-232 only
|
|
|
No hardware handshaking
|
|
EthernetPort
|
10/100Base-T Connector
|
|
|
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
|
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
|
|
|
Link and Data Activity LED indicators
|
|
Serial Ports
|
Not Used
|
Ordering Information
| PTQ-DFNT |
EtherNet/IP Network Interface Module for Quantum |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.