IEC 60870-5-101 Master Network Interface Module for Quantum
PTQ-101M
The IEC 60870-5-101 Master Network Interface Module for Quantum allows Quantum compatible processors to interface easily with IEC 60870-5-101 slave (controlled unit) devices.
Typical applications for this protocol include power distribution, water treatment, lighting systems for highways, etc. Originally developed for the Power Utility industry, the IEC 60870-5 protocols are very similar in function to DNP 3.0. Both protocols offer "Report by Exception" functionality and dating of events (time stamping).
Features & Benefits
|
Feature
|
Benefit
|
|
Standards based
|
Supports IEC 60870-5-101 Master specification: balanced/unbalanced mode, 32 sessions/5 sectors per session, timestamping
|
|
Two configurable IEC-60870-5-101 Master ports
|
Ports individually configurable for com settings, balanced/unbalanced modes, sessions/sectors, commands
|
|
Easy to Configure and Monitor
|
Simple text configuration file configures module, ports, protocol and database settings. Built-in configuration/debug screens allow you to view module status and incoming/outgoing data.
|
|
Three Year Warranty
|
Low risk investment with great cost savings, backed up by a better than average equipment failure protection plan, from the industrial communications experts who know protocols, devices, and automation
|
Configuration
Configuration file in fully commented, easy-to-understand text file format, can be opened with NotePad or any text editor. A sample configuration file is included on the module, on the product CD, or from http://www.prosoft-technology.com. Download configuration file directly to module through the Config/Debug port using HyperTerm or any similar terminal emulation software.
General Specifications
- Single Slot - Quantum backplane compatible
- The module is recognized as an Options module and has access to PLC memory for data transfer
- Configuration data is stored in non-volatile memory in the ProTalk module
- Up to six modules can be placed in a rack
- Local rack - The module must be placed in the same rack as processor
- Compatible with all common Quantum programming packages, including Concept (version 2.6 or higher), Unity Pro (version 2.2 or higher), ProWORX (version 2.20 or later), and ModSoft.
- Quantum data types supported: 3x, 4x
- High speed data transfer across backplane provides quick data update times
- Sample ladder file available
Functional Specifications
|
Specification
|
Description
|
|
Modes
|
Balanced, Unbalanced
|
|
Sessions
|
Up to 32, with up to 5 sectors (separate databases) for each session
|
|
Commands
|
up to 1000
|
|
Pass-through
|
Processor can issue control commands directly to the module or a controlled device (10 at each scan)
Pass-through of event messages from controlled device to processor for logging of time-tagged events
Supports clock synchronization from/to the processor
Receives events from the slave and sends them to the processor
|
|
Monitored data
|
- Single-point
- Double-point
- Step-point
- Measured-point
- Bitstring 32-bit
- Integrated total point
|
|
Delay
|
Class 1 and Class 2 delay parameter in the configuration file
|
Hardware Specifications
|
Backplane Current Load
|
1100 mA maximum @ 5 Vdc ± 5%
|
|
Operating Temperature
|
0°C to 60°C (32°F to 140°F)
|
|
Storage Temperature
|
-40°C to 85°C (-40°F to 185°F)
|
|
Relative Humidity
|
5% to 95% (without condensation)
|
|
Vibration
|
Sine vibration 4 to100 Hz in each of the three orthogonal axes
|
|
Shock
|
30g, 11 mSec. in each of the three orthogonal axes
|
|
Dimensions (HxWxD), Approx
|
250 x 103.85 x 40.34 mm 9.84 x 4.09 x 1.59 in
|
|
LED Indicators
|
Module Status
Backlane Transfer Status
Serial Port Activity LED Serial Activity and Error LED Status
|
|
Configuration Serial Port (PRT1)
|
DB-9M PC Compatible
RS-232 only No hardware handshaking
|
|
Serial Ports
|
(PRT2, PRT3)
DB-9M PC Compatible
RS-232/422/485 jumper selectable
RS-422/485 screw termination included
RS-232 handshaking configurable 500 V Optical isolation from backplane
|
Ordering Information
| PTQ-101M |
IEC 60870-5-101 Master Network Interface Module for Quantum |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|