Johnson Controls Metasys N2 Slave Interface Module

MVI46-N2

The Johnson Controls N2 Communication Module allows Rockwell Automation SLC I/O compatible processors to interface easily with other Johnson Controls N2 master devices.

Features and Benefits

The MVI46-N2 module acts as an input/output module between the Johnson Controls Metasys network and the Rockwell Automation backplane. The module is capable of receiving commands from a master device. The data transfer from the SLC processor is asynchronous from the actions on the Johnson Controls Metasys network. An internal database in the module exchanges data between the processor and the Johnson Controls Metasys Master (NCM, N-30, NAE, NIE).

General Specifications

  • Single Slot - 1746 backplane compatible (Local or extended I/O rack only. Remote rack not supported)
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module using M0/M1 files
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included

Applications

Applications benefiting from the MVI46-N2 module are prevalent in commercial building and energy management projects. Single or multiple processor applications will benefit through reduced installation costs and increased functionality.

Functional Specifications

Some of the general specifications include:

  • Support for the storage and transfer of internal database registers to/from the SLC processor's controller tags
  • Two ports to emulate a Johnson Controls N2 slave
  • Supports the following N2 objects:
    • Binary Input: Up to 960 points
    • Analog Input: Up to 300 points
    • Binary Output: Up to 960 points
    • Analog Output: Up to 300 points
  • Supported Commands/Sub-commands
    • 0/4: Poll Message No Acknowledge
    • 0/5: Poll Message with Acknowledge
    • 0/9: Status Update
    • 1/1: Read Analog Input Attributes
    • 1/2: Read Binary Input Attributes
    • 1/3: Read Analog Output Attributes
    • 1/4: Read Binary Output Attributes
    • 2/1: Write Analog Input Attributes
    • 2/2: Write Binary Input Attributes
    • 2/3: Write Analog Output Attributes
    • 2/4: Write Binary Output Attributes
    • 7/2/3: Override Analog Output
    • 7/2/4: Override Binary Output
    • F: Identify Device Type
  • The following commands are recognized, and acknowledged, but are not communicated in any way to the PLC/SLC, and do not return any data:
    • 0/0: Time Update
    • 0/8: Warm Start
    • All other commands return a Bad Command Error Code
  • Configurable through the configuration file for the following:
    • Slave Address (assignable individually for Port 1 and 2)
    • Analog Input Object Count
    • Binary Input Object Count
    • Analog Output Object Count
    • Binary Output Object Count
  • Warning and Alarming functions performed on Analog Input and Binary Input data types
  • Change of State Response buffering
  • Communication status error codes and statistics returned per port
  • Memory mapping is pre-assigned to optimize data access and to ease implementation
  • A port configured as a Johnson Controls N2 slave permits a remote master to interact with data contained in the module. This data is derived from the SLC processor.

Hardware Specifications

Application Serial ports
(P1, P2)

 
 

Full hardware handshaking control, providing radio, modem, and multi-drop support

Software configurable communication parameter

Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms
RS-232 handshaking configurable

App Ports (P1, P2)

RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable)
500V optical isolation from backplane

CFG Port

RJ45 (DB-9M with supplied cable)
RS-232 only

Shipped with unit

RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port

Specification

Description

Backplane Current Load

800 ma @ 5V (from backplane)

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Shock

30g operational, 50g non-operational

Relative Humidity

5 to 95% (non-condensing)

Vibration

5 g from 10150 Hz

Processor

Compatible with Rockwell Automation SLC 5/02 M0/M1 capable processors or newer.

LED indicators

Module status, Backplane transfer status, Application status, Serial activity and error LED status

Ordering Information

MVI46-N2 Johnson Controls Metasys N2 Slave Interface Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested