Modbus TCP/IP Communication Client Module
MVI46-MNETC
The MVI46 Modbus TCP/IP Client Communication Module is designed to allow SLC processors to interface easily with other Modbus TCP/IP protocol-compatible devices.
Compatible devices include not only Modicon processors (which support the Modbus TCP/IP protocol) but also a wide assortment of other server devices.
Features and Benefits
This module was created to improve the performance when servers are not needed on a Modbus TCP/IP network. The module supports up to 30 clients with up to 16 commands for each client, making it easy to enable/disable the commands from the ladder logic. The client command control word contains one bit for each command.
Some of the other features include:
- Support for the storage and transfer of up to 5000 registers to/from the SLC processor's controller tags
- Module memory usage that is completely user definable
- 10/100 MB Ethernet compatible interface
- Configurable parameters for the client include:
- Minimum Command Delay
- User Defined Commands (Read/Write)
General Specifications
- Single Slot - 1746 backplane compatible (Local or extended I/O rack only. Remote rack not supported)
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module using M0/M1 files
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
Applications
With the growing trend of Ethernet technology in the industrial marketplace, this product has a wide variety of application uses.
- Food processing
- Petrochemical
- Pulp and paper
- Automobile manufacturing
- Water and Wastewater
- Oil and Gas
- Power and Electric
Functional Specifications
- Operation via simple ladder logic
- Complete set up and monitoring of module through software and user-constructed configuration file (MNET.CFG)
- Backplane interface via I/O access
General Protocol specifications
|
Type
|
Specifications
|
|
Floating Point Data
|
Floating point data movement supported, including configurable support for Enron implementation
|
Modbus TCP/IP Client
- The client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.
- Up to 30 client connections available.
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 ma @ 5V (from backplane)
|
|
Operating Temperature
|
0 to 60°C (32 to 140°F)
|
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
|
Shock
|
30g operational, 50g non-operational
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
Vibration
|
5 g from 10150 Hz
|
|
Processor
|
Compatible with Rockwell Automation SLC 5/02 M0/M1 capable processors or newer.
|
|
LED indicators
|
Module status, Backplane transfer status, Application status, Serial activity and error LED status
|
|
Ethernet and CFG Ports
|
|
|
Ethernet Port
|
RJ45 connection
10/100 Mbit Ethernet support (auto-sensing)
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for debug port
|