Application Development Module with EtherNet

MVI46-ADMNET

The MVI46 Application Development Ethernet Communication Module is an SLC backplane compatible module that allows Rockwell Automation SLC processors to interface easily with Ethernet protocol compatible devices and hosts.

Features

The ADMNET solution is a powerful module designed with both Client and Server support. This broad support enables the module to function as a data collection sub-master, or to be a powerful slave as a remote off an HMI host. Applications for the module are found in most industries, especially Manufacturing, Oil and Gas, Electrical Power and Food processing.

The MVI46-ADMNET module is a single slot, backplane compatible solution for the Rockwell Automation SLC platform. This module is a powerful and programmable solution supporting two fully isolated serial ports and one Ethernet port allowing the many field devices to be integrated into the SLC platform with custom user written 'C' code and various APIs supplied for Ethernet, serial and backplane communication.

General Specifications

  • Single Slot - 1746 backplane compatible (Local or extended I/O rack only. Remote rack not supported)
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module using M0/M1 files
  • Ladder Logic is used for data transfer between module and processor
  • Configuration data obtained through user-defined ladder. Sample ladder file included

Applications

The MVI46-ADMNET module is the ideal solution for many applications where Ethernet and serial connectivity must be added to an SLC platform. Applications using the MVI46-ADMNET module:

  • Bar code scanner interface
  • Legacy ASCII protocol connections
  • Terminal port emulation
  • Printer driver (alarm/status printer)
  • Customized protocol implementations

Functional Specifications

The MVI46-ADM API Suite allows software developers access to the top layer of the SLC backplane and serial ports. The MVI46-ADMNET API suite accesses the Ethernet port and serial ports.

Both APIs can be easily used without having detailed knowledge of the module's hardware design. The Ethernet Port API provides access to the Ethernet network. Applications for the MVI46-ADMNET module may be developed using industry-standard DOS programming tools and the appropriate API components.

The MVI46-ADMNET module has three serial ports, two of which are isolated for field interfaces, and one Ethernet port.

  • CFG -- debug/configuration -- RS-232
  • PRT1 -- Application -- RS-232, RS-422 or RS-485
  • PRT2 -- Application -- RS-232, RS-422 or RS-485
  • Ethernet Port

PRT1 and PRT2 are jumper configured for direct or Multidrop field communication. The application program can be written to control the two application ports independently, allowing maximum flexibility in the design.

General Protocol Specifications

  • Allows software developers to access Rockwell Automation backplane and Serial/Ethernet ports to communicate with various field devices, without needing detailed knowledge of the module's hardware design
  • API library functions are specified using the C programming language syntax
  • The following compiler versions are compatible with the MVI module API:
    • Digital Mars C++ 8.49
    • Borland C++ V5.02
  • Operating System - General software DOS 6-XL
  • Flash ROM program space: 896 KB
  • RAM program and data space: 640 KB
  • Compact Flash socket: Supports up to 16G Microdrive (not supplied)

ADM API Libraries

  • Each API provides a library of function calls. This library supports any programming language that is compatible with the Pascal calling convention.
  • Initialization - Open and close the API
  • Debug Port - Debug port user interface
  • Database - Read and write data to database
  • Timer - Start and check timers
  • Backplane - Transfer data over the backplane
  • LED - Set user LED indicators
  • Flash - Parse configuration files
  • Miscellaneous - Configure the console

Hardware Specifications

Application Ports (PRT1 and PRT2)

 
 

Full hardware handshaking control, providing radio, modem, and multi-drop support

Software configurable communication parameters

Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd, or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535ms
RS-232 handshaking configurable

Serial Application Ports

RJ45 (DB-9M with supplied cable)
RS-232, 485 and 422 (jumper selectable)
500V optical isolation from backplane

Ethernet Port

RJ45 connection
10/100 Mbit Ethernet support (auto-sensing)
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

CFG Port

RJ45 (DB-9M with supplied cable)

RS-232 only

Shipped with unit

RJ45 to DB-9M adapter cable for each port

Six foot RS-232 configuration cable for debug port

Specification

Description

Backplane Current Load

800 ma @ 5V (from backplane)

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Shock

30g operational, 50g non-operational

Relative Humidity

5 to 95% (non-condensing)

Vibration

5 g from 10150 Hz

Processor

Compatible with Rockwell Automation SLC 5/02 M0/M1 capable processors or newer.

LED indicators

Module status, Backplane transfer status, Application status, Serial activity and error LED status

Ordering Information

MVI46-ADMNET Application Development Module with EtherNet
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested