EtherNet/IP Interface Module
MVI71-DFNT
The MVI71 EtherNet/IP (DF1 for Ethernet) Client/Server Communication Module is a PLC backplane compatible module that allows PLC processors to interface easily with EtherNet/IP protocol (Explicit Messaging) compatible devices and hosts. Devices commonly supporting the protocol include Rockwell Automation PLCs, and host HMI systems.
Features and Benefits
The MVI71-DFNT module is a single slot solution that provides a powerful connection between Rockwell Automation's PLC processor and EtherNet/IP (DF1 for Ethernet) network applications.
The module can send read or write commands to remote devices on the EtherNet/IP network. The MVI71-DFNT also has 20 servers that allows the module to receive commands from remote devices. The MVI71-DFNT Pass-Through server allows the user to edit and transfer the PLC ladder logic using an Ethernet connection. Up to 100 commands can be configured by the user.
Configuration
ProSoft Configuration Builder (PCB) provides a PC-based software configuration solution for quick management of configuration files, as well as viewing communication and network diagnostics. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations into new projects.
General Specifications
- Single Slot - 1771 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
EtherNet/IP (Explicit Messaging) Compatible Devices
Rockwell Automation equipment that supports EPIC:
- SLC5/05 series A, OS503 frn4
- 1785-ENET Series A, rev D
- Interchange V6.2
- MicroLogix 1100/1400/ANY via 1761-NET-ENI
- CompactLogix 1768-L43/L45 via 1768-ENBT
- CompactLogix 1769-L32E/L35E/ANY
- CompactLogix L23E
- RSLinx Gateway V1.7+
- ControlLogix 1756-ENET/ENBT/EN2T/EN2TR
Functional Specifications
- PLC processor in-chassis EtherNet/IP bridge to optimize data throughput while communicating with HMI or SCADA and other control platforms without losing valuable process control bandwidth
- Support of up to 4000 PLC registers user data files
- User-definable module memory usage
- 10/100 MB Ethernet compatible interface
- Functions as a server or a client
- Configurable parameters for the client include:
- A minimum response delay of 0 to 65535 mSec
- A response timeout of 1 to 65535 mSec
- A retry count of 0 to 20
- Status data available in ladder logic
Support for PLC processor programming over Ethernet using a TCP/IP service and a serial port on the module connected to channel 0 of the processor. The module's third port emulates Channel 0 of the processor to pass through messages from the port to the processor
Server Specifications
- Supports EtherNet/IP explicit, connected, and unconnected class messaging
- Twenty independent server connections permit remote clients to interact with all data contained in the module
- Data can be derived from other clients on the network, through the client on the module, or from the PLC processor
Client Specifications
- Actively issues connected, explicit messages to other nodes on the network
- Supports 100 user-defined commands from a single client
- Allows command control from ladder logic
- Pass-through services
- Permits remote programming of the PLC processor on the Ethernet network via a pass-through
- TCP/IP service and a serial communication port (pass-through port) on the module
- The third port on the module can emulate the Channel 0 port on the PLC, This allows a DF1 master device attached to the emulated (Channel 0) port to monitor and control data in the PLC.
Hardware Specifications
|
Form Factor
|
Single Slot - 1771 chassis compatible
|
|
|
BTR/BTW data transfer
|
|
|
Local or remote rack
|
|
Backplane Current Load
|
800 mA @ 5V
|
|
Operating Temperature
|
32°F to 140°F (0°C to 60°C)
|
|
Storage Temperature
|
-40°F to 185°F(-40°C to 85°C)
|
|
Shock
|
30g operational
|
|
|
50g non-operational
|
|
Vibration
|
5g from 10 Hz to 150 Hz
|
|
Relative Humidity
|
5% to 95% RH, with no condensation
|
|
LED Indicators
|
Module status
|
|
|
Backplane transfer status
|
|
|
Application status
|
|
|
Error LED status
|
|
|
Link and Activity LED
|
|
Configuration Port (CFG)
|
DB-9M PC compatible
|
|
|
RS-232
|
|
|
Hardware handshaking
|
|
Ethernet Port
|
RJ45 connector
|
|
|
10/100 Mbit Ethernet support (auto-sensing)
|
|
|
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991
|
|
|
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable for configuration
|
|
|
6-foot RS-232 null-modem configuration cable
|
|
|
|
Ordering Information
| MVI71-DFNT |
EtherNet/IP Interface Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.