'C' Programmable Communication Module for FLEX I/O
MVI94-ADM
The MVI94 Application Development Module is a FLEX backplane compatible module that allows user-developed "C" applications to operate on the FLEX platform. A great way to speed up custom ASCII data communications or to protect a proprietary algorithm, the ADM is a powerful tool for the FLEX platform.
Features and Benefits
Powerful platform for developing and running 'C' applications on Rockwell Automation's FLEX I/O processors. The MVI94-ADM module is a single slot, backplane compatible solution for the Rockwell Automation FLEX I/O and Integra I/O platforms. This module is a powerful and programmable solution supporting two fully isolated serial ports allowing serial field devices to be integrated into the FLEX platforms.
The MVI94-ADM module has two serial ports, both of which are isolated for field interfaces:
- PRT1 Application/Debug/Config RS-232
- PRT2 Application RS-232, RS-422 or RS-485
PRT2 is jumper configured for direct or Multidrop field communication. The application program can be written to control the two application ports independently, allowing maximum flexibility in the design.
General Specifications
Some of the general specifications include:
- Operation via simple ladder logic
- Complete setup and monitoring of module through Debug port and user configuration file
- Flex backplane interface via I/O access
Applications
The MVI94-ADM module is the ideal solution for many applications where serial connectivity must be added to a FLEX platform. Applications using the MVI94-ADM module include:
- Bar code scanner interface
- Legacy ASCII protocol connections
- Terminal port emulation
- Printer driver (Alarm/status printer)
- Customized protocol implementations
Functional Specifications
Development Environment
- Operating system: General software DOS 6-XL
- Compatible compiler (16-bit DOS target)
- Digital Mars C++ V8.49
- Borland C++ V5.02
Application Programming Interfaces (API)
- Serial Port API: serial port functions
- Backplane API: low level backplane functions
- ADM API debug port functions: debug port functions, database functions timer functions, high level backplane transfer functions, LED functions, flash read functions
Hardware Specifications
|
Specification
|
Description
|
|
Form Factor
|
Single Slot 1794 Backplane compatible Locate in any slot of Backplane
|
|
Backplane current load
|
20 mA @ 5 V
|
|
External power supply
|
12V to 24VDC 340 ma to 170 ma
|
|
Operating temperature
|
0 to 55°C (32 to 131°F)
|
|
Storage temperature
|
-40 to 85°C (-40 to 185°F)
|
|
Shock
|
30g operational
50g non-operational 5g from 10150 Hz
|
|
Relative humidity
|
5 to 95% (non-condensing)
|
|
LED indicators
|
Module status
Backplane transfer status
Application status Serial activity and error LED status
|
|
Configuration Serial port (PRT1)
|
Mini-DIN
RS-232 Hardware handshaking
|
|
Application serial Port (PRT2)
|
Mini-DIN
RS-232/422/485 jumper selectable 500V optical isolation from backplane
|
|
Dimensions (with Module installed in Base)
|
3.7H x 3.7W x 2.7D inches 94H x 94W x 69D mm
|
Ordering Information
| MVI94-ADM |
'C' Programmable Communication Module for FLEX I/O |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.