AB-PCCC Communications interface Module for ControlLogix by FieldServer Technologies
PS56-PRO-407
The AB_CSP driver implements the Allen Bradley Ethernet protocol commonly referred to as the CSP, using PCCC message structures. The AB_CSP driver allows the SlotServer to transfer data to and from devices over AB_CSP Ethernet protocol. The SlotServer can emulate either a Server or Client.
Comes with the standard two-year FieldServer warranty.
Read Operations Supported
Allen Bradley commands can be specified directly using the AB Command map descriptor field, or can be implied using the Node field PLC Type. the AB command will override any PLC Type specifiers.
Command
|
AB Command
|
PLC Type
|
File Type
|
SlotServer as a Client
|
|
Unprotected Read
|
Unprotected
|
-
|
All
|
|
Protected Typed Logical Read
|
Protected Typed Logical
|
-
|
All
|
|
Typed Read
|
Typed
|
-
|
All
|
|
Protected Typed Logical Read
|
-
|
SLC5
|
N,F,B,I,O
|
|
Word Range Read
|
-
|
PLC3/PLC5
|
N,F,B
|
SlotServer as a Server
When configured as a server, the driver is passive on the network, meaning it will respond to all polls it receives from an AB_CSP Client.
|
Write Operations Supported
|
Command
|
AB Command
|
PLC Type
|
File Type
|
SlotServer as a Client
|
|
Unprotected Write
|
Unprotected
|
-
|
All
|
|
Typed Write
|
Typed
|
-
|
All
|
|
Protected Typed Logical Write
|
-
|
SLC5
|
N,F,B
|
|
Word Range Write
|
-
|
PLC5
|
N
|
|
Typed Write
|
-
|
PLC5
|
F
|
|
Read Modify Write
|
-
|
PLC5
|
B
|
|
Word Range Write
|
-
|
PLC3
|
N,F
|
|
Bit Write
|
-
|
PLC3
|
B
|
SlotServer as a Server
When configured as a server, the driver is passive on the network, meaning it will respond to all polls it receives from an AB_CSP Client.
|
Supported Data Types
|
Data Type
|
Description
|
|
N
|
INTEGER
|
|
B
|
BINARY
|
|
F
|
FLOAT
|
|
O
|
OUTPUT
|
|
I
|
INPUT
|
|
T
|
TIMER
|
|
S
|
STATUS
|
Unsupported Data Types
|
|
C
|
Counter
|
|
ST
|
ASCII String
|
|
T
|
Timer
|
Hardware Specifications
|
Slot Width
|
Single
|
|
Backplane Current Load
|
600 mA @ 5 Vdc
|
|
Operating Temperature
|
0°C to 60°C (32°F to 140°F)
|
|
Storage Temperature
|
-40°C to 85°C (-40°F to 185°F)
|
|
Humidity
|
5% to 95%, with no condensation
|
|
Allen-Bradley Paltform
|
ControlLogix 1756 chassis
|
|
Connections
|
TP/FT-10 (LonWorks network)
RS-485 (two-wire, serial network) RJ-45 (Ethernet network)
|
|
LED Indicators
|
Module Status
Backplane Transfer Status
Communication Status
Configuration Error
System Error
Serial Activity
Ethernet Activity 10/100BaseT Indicator
|
|
Display
|
Scrolling display of module messages
|
|
Service Pin
|
For LonWorks commissioning
|
|
Mounting
|
Local or Remote chassis
|
|
Approval
|
UL60950
|
|
Configuration
|
Configuration data is contained in the configuration CSV file downloaded to the module. Sample configuration file is included.
|
Ordering Information
| PS56-PRO-407 |
AB-PCCC Communications interface Module for ControlLogix by FieldServer Technologies |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|