ProSoft Technology, Inc.
Home > Products > for Rockwell Automation > Platform > ControlLogix > MVI56-N2
Printable Page
 

Search | Clear


Johnson Controls Metasys N2 Slave Interface Module

MVI56-N2

The MVI56 Johnson Controls Metasys Slave Communication Module allows Rockwell Automation ControlLogix I/O compatible processors to interface easily with other Johnson Controls N2 master devices.

Features and Benefits

The MVI56-N2 module acts as an input/output module between the Johnson Controls Metasys network and the Rockwell Automation ControlLogix backplane. The module acts as a slave receiving commands from a master device. The data transfer from the ControlLogix processor is asynchronous from the actions on the Johnson Controls Metasys network. An internal database in the module exchanges data between the processor and the Johnson Controls Metasys Master (NCM, N-30, NAE, NIE).

General Specifications

  • Single Slot - 1756 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
  • Local or remote rack

Applications

Ideal for Energy Management Applications.

Applications benefiting from the N2 module are prevalent in commercial building and energy management projects. Single or multiple processor applications will benefit through reduced installation costs and increased functionality.

Functional Specifications

  • Support for the storage and transfer of internal database registers to/from the ControlLogix processor's controller tags
  • Two ports to emulate a Johnson Controls N2 slave
  • Supports the following N2 objects:
    • Binary Input: Up to 960 points
    • Analog Input: Up to 255 points
    • Binary Output: Up to 960 points
    • Analog Output: Up to 255 points
  • Supported Commands/Sub-commands
    • 0/4: Poll Message No Acknowledge
    • 0/5: Poll Message with Acknowledge
    • 0/9: Status Update
    • 1/1: Read Analog Input Attributes
    • 1/2: Read Binary Input Attributes
    • 1/3: Read Analog Output Attributes
    • 1/4: Read Binary Output Attributes
    • 2/1: Write Analog Input Attributes
    • 2/2: Write Binary Input Attributes
    • 2/3: Write Analog Output Attributes
    • 2/4: Write Binary Output Attributes
    • 7/2/3: Override Analog Output
    • 7/2/4: Override Binary Output
    • F: Identify Device Type
  • The following commands are recognized, and acknowledged, but are not communicated in any way to the ControlLogix , and do not return any data:
    • 0/0: Time Update
    • 0/8: Warm Start
    • All other commands return a Bad Command Error Code
  • Configurable through the configuration file for the following:
    • Slave Address (assignable individually for Port 1 and 2)
    • Analog Input Object Count
    • Binary Input Object Count
    • Analog Output Object Count
    • Binary Output Object Count
  • Warning and Alarming functions performed on Analog Input and Binary Input data types
  • Change of State Response buffering
  • Communication status error codes and statistics returned per port
  • Communication parameter: Baud rate 9600 bps.

Memory mapping is pre-assigned to optimize data access and to ease implementation

A port configured as a Johnson Controls N2 slave permits a remote master to interact with data contained in the module. This data is derived from the ControlLogix processor.

Hardware Specifications

Application Serial ports
(P1, P2)

 
 

Full hardware handshaking control, providing radio, modem, and multi-drop support

Software configurable communication parameter

Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms
RS-232 handshaking configurable

App Ports (P1, P2)

RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable)
500V optical isolation from backplane

CFG Port

RJ45 (DB-9M with supplied cable)
RS-232 only

Shipped with unit

RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port

Specification

Description

Backplane Current Load

800 mA @ 5 V

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Shock:

30g Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz

Relative Humidity

5 to 95% (non-condensing)

LED Indicators:

Module Status
Backplane Transfer Status
Application Status
Serial Activity

Ordering Information

MVI56-N2 Johnson Controls Metasys N2 Slave Interface Module
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested