Modbus TCP/IP Client Communication Module with Reduced Data Block

MVI56-MNETCR

The MVI56 Modbus TCP/IP Client Communication Module with Reduced Data Block is designed to allow ControlLogix processors to interface easily with other Modbus TCP/IP protocol-compatible devices. Compatible devices include not only Modicon processors (which support the Modbus TCP/IP protocol) but also a wide assortment of other server devices.

This module uses a small I/O data area for data transfer between the module and the ControlLogix processor, making it ideal for ControlNet or Ethernet applications with the module in a remote rack.

Features and Benefits

This module was created to improve the performance when servers are not needed on a Modbus TCP/IP network. The module supports up to 30 clients with up to 16 commands for each client, making it easy to enable/disable the commands from the ladder logic. The client command control word contains one bit for each command.

Some of the other features include:

  • Support for the storage and transfer of up to 5000 registers to/from the ControlLogix processor's controller tags
  • Module memory usage that is completely user definable
  • 10/100 MB Ethernet compatible interface
  • Configurable parameters for the client include:
    • Minimum Command Delay
    • User Defined Commands (Read/Write)

General Specifications

  • Single Slot - 1756 backplane compatible
  • The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
  • Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
  • Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
  • This module uses a small I/O data area for 40 word data block transfer between the module and the ControlLogix processor, for applications with the module in a remote rack.

Applications

With the growing trend of Ethernet technology in the industrial marketplace, this product has a wide variety of application uses.

  • Food processing
  • Petrochemical
  • Pulp and paper
  • Automobile manufacturing
  • Water and Wastewater
  • Oil and Gas
  • Power and Electric

Functional Specifications

The MVI56-MNETCR transmits smaller data packets than the MVI56-MNETC, which makes it ideal for remote rack or where bandwidth is limited.

  • 40 word data blocks (scheduled)
  • Special functions (command control, event commands, status, etc.) are supported by unscheduled instructions
  • Operation via simple ladder logic
  • Complete set up and monitoring of module through software and user-constructed configuration file (MNET.CFG)
  • Backplane interface via I/O access

General Protocol specifications

Type

Specifications

Floating Point Data

Floating point data movement supported, including configurable support for Enron implementation

Modbus TCP/IP Client

  • The client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices.
  • Up to 30 client connections available.

Hardware Specifications

Ethernet and CFG Ports

 

Ethernet Port

RJ45 connection
10/100 Mbit Ethernet support (auto-sensing)
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

CFG Port

RJ45 (DB-9M with supplied cable)
RS-232 only

Shipped with unit

RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for debug port

Specification

Description

Backplane Current Load

800 mA @ 5 V

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Shock:

30g Operational
50g non-operational
Vibration: 5 g from 10 to 150 Hz

Relative Humidity

5 to 95% (non-condensing)

LED Indicators:

Module Status
Backplane Transfer Status
Application Status
Serial Activity

Ordering Information

MVI56-MNETCR Modbus TCP/IP Client Communication Module with Reduced Data Block
   
To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here.

 

Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.

Sales and Support:

Asia Pacific
+603.7724.2080
asiapc@prosoft-technology.com
Europe
+33 (0)5.34.36.87.20
europe@prosoft-technology.com
Latin America
Office: +1 281.298.9109
Mobile: +1-281-830-8946
latinam@prosoft-technology.com
North America
+1 661.716.5100
Fax: +1 661.716.5101
info@prosoft-technology.com

 

Related Information

ProSoft Configuration Builder

Image Gallery



Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested