MDA Scientific System 16 Slave Module
MVI56-MDA16
The MVI56 MDA Scientific System 16 Gas Analyzer Slave Module allows Rockwell Automation ControlLogix processors to interface easily as a host with MDA Scientific CM4 gas monitoring hardware (See MVI56-MDA4 for a CM4 solution).
Features and Benefits
The MVI56-MDA16 module acts as an input/output module between the System 16 network and the Rockwell Automation backplane. The data transfer from the ControlLogix processor is asynchronous from the actions on the System 16 network. A 1600-word register space in the module is used to exchange data between the processor and the System 16 network.
General Specifications
- Single Slot - 1756 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
- Local or remote rack
Applications
This application is useful for any industry producing, using, or exposed to toxic or corrosive gases, where interfacing the System 16 Gas Analyzer with a ControlLogix processor is required.
Functional Specifications
- Support for the storage and transfer of up to 1600 registers to/from the ControlLogix processor's data files
- Two System 16 slave ports.
- Configurable parameters include:
- Baud Rate 110 to 115,200
- Parity None, Odd and Even
- Data Bits 5 to 8
- Stop Bits 1 or 2
- RTS On and Off Timing 0 to 65535 milliseconds
- Use of CTS Modem Line Yes or No
Operating Specifications
The MDA-16 product includes the following standard features:
- Two fully configurable serial ports, each capable of supporting the System 16 Slave functionality
- Supports one System 16 unit per serial port, 2 total per module
- Memory mapping will be pre-defined in the module to ease implementation in the ladder program
- RS-485 connection from each port directly to the System 16 unit
- Supported System 16 command codes:
- Write Commands
- 0x30 Sequential Sample Results
- 0x50 System Configuration
- 0x52 Point Enable Masks
- 0x53 Current System State
- 0x54 Point Configuration
- 0x56 Gas Table Data
- 0x61 Fault
- 0x68 Fault and Alarm Reset
- Operating Mode returned to ladder processor
- Error Codes returned to the ladder processor
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 mA @ 5 V
|
|
Operating Temperature
|
0 to 60°C (32 to 140°F)
|
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
|
Shock:
|
30g Operational
50g non-operational Vibration: 5 g from 10 to 150 Hz
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
LED Indicators:
|
Module Status
Backplane Transfer Status
Application Status Serial Activity
|
|
Application Serial ports (P1, P2)
|
|
|
|
Full hardware handshaking control, providing radio, modem, and multi-drop support
|
|
Software configurable communication parameter
|
Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms RS-232 handshaking configurable
|
|
App Ports (P1, P2)
|
RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable) 500V optical isolation from backplane
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port
|
Ordering Information
| MVI56-MDA16 |
MDA Scientific System 16 Slave Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|