DNP 3.0 over Ethernet Server Communications Interface Module
MVI56-DNPSNET
The MVI56 DNP 3.0 Server Ethernet Communications Module supports the implementation of the DNP 3.0 (Distributed Network Protocol) over Ethernet, allowing ControlLogix processors to easily communicate with host systems supporting the protocol. The module supports DNP Subset Level 2 features and some Level 3 features.
Features and Benefits
The MVI56-DNPSNET (Distributed Network Protocol Module over Ethernet) allows Rockwell Automation ControlLogix processors to easily communicate with other DNP protocol-compatible devices.
The module supports DNP subset level 2 features and some Level 3 features. The MVI56-DNPSNET module acts as an input/output module between the DNP Ethernet network and the Rockwell Automation backplane. The data transfer from the ControlLogix processor is asynchronous from the actions on the DNP network. Databases are defined in the module to house the data required by the protocol.
General Specifications
- Single Slot - 1756 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
- Local or remote rack
Applications
With the growing usage of the DNP protocol over Ethernet technology in the industrial marketplace, this product has a wide variety of application uses. Industries that use this technology include:
- Power and distribution applications
- Petrochemical
- Water and Gas Applications
- SCADA and DCS applications
Functional Specifications
The MVI56-DNPSNET module accepts DNP commands to control and monitor the data stored in the DNP databases. This data is passed between the module and the ControlLogix processor over the backplane for use in user applications.
- DNP databases to house data for the slave port supporting the following maximum input counts
- Binary input: 8000 points (500 words)
- Binary output: 8000 points (500 words)
- Counter: 250 (500 words)
- Analog input: 500
- Analog output: 500
- Module memory usage that is definable up to maximum point counts
- Data movement between module using block-transfer
- Ethernet port supporting both TCP and UDP over Ethernet
- Supports DNP 3.0 in a level 2 implementation
- Supports sending of input event data from the ladder to the module
- Supports time synchronization from/to processor
- Configurable via text file
- Status and error information
- All data in the DNP slave is contained in user-defined files
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 mA @ 5 V
|
|
Operating Temperature
|
0 to 60°C (32 to 140°F)
|
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
|
Shock:
|
30g Operational
50g non-operational Vibration: 5 g from 10 to 150 Hz
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
LED Indicators:
|
Module Status
Backplane Transfer Status
Application Status Serial Activity
|
|
Ethernet and CFG Ports
|
|
|
Ethernet Port
|
RJ45 connection
10/100 Mbit Ethernet support (auto-sensing)
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for debug port
|
Ordering Information
| MVI56-DNPSNET |
DNP 3.0 over Ethernet Server Communications Interface Module |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|