Siemens 3964R Protocol
MVI56-3964R
Important! Please Read!
Product Discontinuation Notice
MVI56-3964R will be discontinued effective 06/15/2007. ProSoft offers an improved implementation of the Siemens 3964R protocol in the new MVI56-S3964R module, which is available now.
Please review the Product End of Life Notification for important information on ordering, replacement and support for MVI56-3964R.
The MVI56 3964R Protocol module from ProSoft Technology allows point-to-point communication between a ControlLogix controller (1756-L1, -L1Mx, L55, L63) and a partner with 3964R (with or without RK512) communication capability.
Features and Benefits
The 3964R protocol (with or without RK512) was designed by Siemens for bi-directional data communication through a point-to-point connection. It is a master-slave protocol with read and write access. A BCC checksum ensures the safety of the transfer.
General Specifications
- Single Slot - 1756 backplane compatible
- Local or remote rack
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor.
- Configuration data obtained through user-defined ladder. Sample ladder file included.
Applications
The module is ideal in control configurations where there is a need for the ControlLogix controller to exchange data with other non-Rockwell Automation control devices in low speed applications.
The MVI56-3964R can communicate with or without RK512 devices using two RS-232, RS-422 communication lines (ports). The ports operate independently from each other.
Functional Specifications
- Single-slot, ControlLogix backplane compatible
- Multiple modules can be placed in a rack up to the chassis power supply limit
- While in 3964R with RK512 mode on PRT1 and PRT2, DB-SEND and DB-FETCH instructions can be initiated from the ControlLogix processor or received by the communications partner
- While in 3964R without RK512 mode on PRT1 and PRT2, data can be sent from the ControlLogix processor or be received from the communications partner
- The maximum transfer rate is 512 bytes in any mode
- Data byte swapping can be configured to adjust to a different word format
- While in 3964R with RK512 mode on PRT1 and PRT2, evaluation of the header information DB (data block), DW (data word) and coordination bytes 9 and 10 is possible
- Communication activity and diagnostics are available through LEDs and acknowledgment telegrams
- Example programs are provided for using the 3964R protocol with a Siemens ASM 420 / ASM 424 MOBY-I/E communication interface
Ladder Logic
Ladder logic programming in the ControlLogix processor is required in order to enable and support the Siemens 3964R protocol functionality. The ladder program handles the encoding/decoding of data transferred from the module as well as the initiation of protocol-specific functionality in the module. Example ladder programs are provided with the module to ease the implementation of the module in the user application.
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 mA @ 5 V
|
|
Operating Temperature
|
0 to 60°C (32 to 140°F)
|
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
|
Shock:
|
30g Operational
50g non-operational Vibration: 5 g from 10 to 150 Hz
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
LED Indicators:
|
Module Status
Backplane Transfer Status
Application Status Serial Activity
|
|
Application Serial ports (P1, P2)
|
|
|
|
Full hardware handshaking control, providing radio, modem, and multi-drop support
|
|
Software configurable communication parameter
|
Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms RS-232 handshaking configurable
|
|
App Ports (P1, P2)
|
RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable) 500V optical isolation from backplane
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port
|
Ordering Information
| MVI56-3964R |
Siemens 3964R Protocol |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|